Coal
Coal is an abundant and relatively inexpensive fuel
on a dollar per BTU basis in North America. Fifty-Five percent of the
United States' utilities' net electric generation comes from coal. However,
coal fired power plants are complicated, largely due to the coal handling
equipment and strict environmental regulations, and are generally more
expensive to build than oil or natural gas.
The coal is most often delivered to the power plant
using trucks and stored on a stock pile which usually contains a 30 to
60 day supply. The coal is transported from the storage pile to the plant
where it is ground into a fine powder and burned in the boiler.
Coal presents several environmental challenges in that
it produces more combustion byproducts than either oil or gas. Burning
coal produces four main byproducts which must be carefully controlled
in compliance with strict federal regulations. Theses include fly ash,
bottom ash, nitrogen oxides, and sulfur oxides. Many utilities sell fly
ash to concrete companies to be used as a concrete additive. Bottom ash
is collected and stored until it can be ground up and used as a concrete
additive and for stabilizing road beds. Scrubbers and other equipment
are used to clean and limit the amount of sulfur oxides ad nitrogen oxides
released through the stack.
Generation Dispatch
Electricity is unique in that it must be produced the
instant it is needed. It just cannot be economically stored in large
quantities using today's technology. And, unlike telephone service, power
users do not tolerate a busy signal.
The utility normally tries to schedule and operate a
series of generators at a given power level known to be the most efficient
for the season and time. As the customers' needs for power change, the
operators must adjust the amount of electricity produced by various generation
units. If the required load is higher than what the generators are currently
producing, the system's electrical frequency falls below the desired
value of 60 cycles. The generation operators decide which unit is the
most economical to increase power output, or they bring an additional
generating unit on line to raise the frequency back up to 60 cycles.
If the generators are producing too much electricity compared to what
the required load is, the system frequency increases above 60 cycles
and the generation operators decide which unit's power generation needs
to be lowered.
In the event the electric utility doesn't generate the
required power when it is needed, the system voltage drops below the
minimum set point, and circuit breakers begin to trip to prevent equipment
damage. This can cause major power outages for consumers. Fortunately,
today's electric utilities have interchange agreements with other power
suppliers that minimize the likelihood of this happening.
Electric utilities also plan their power generation
to meet widely varying demands during the year, and during any given
day. Because of the varied schedules on which customers use electricity,
the load varies over the day, the week, and the year. Normally, the load
tends to be lowest at night, when most people are asleep, and highest
during the day, when the most appliances are in use. Some utilities see
a peak at night due to electric space heating in the cooler months, while
most utilities see a peak during the hottest days of the summer when
air conditioners are working their hardest.
When a utility has its highest demand for power in the
winter, it is referred to as winter peaking. When the demand for power
is highest in the summer, it is called summer peaking.
Delivery
Delivery System Overview
As electrical energy is generated, it is transformed
and transported instantaneously through a network of wires, substations,
and transformers to the consumer. Electricity is generated at a comparatively
low voltage at most generating stations. In order to transport this energy
great distances, the voltage has to be increased, or stepped up; to values
as high as 765,000 volts. This is accomplished through the use of large
transformers located near the generation station, and provides an efficient
and economical method of transmission. Transmission line voltages can
range from 69,000 volts to 765,000 volts.
From the generating station to the final destination,
the energy from generated electricity undergoes numerous changes in voltage
and direction. Each change requires expert design and handling to provide
the consumer with the least expensive, most reliable energy they can
buy.
Distribution System
The purpose of the distribution system is to distribute
the electricity to each customer's residence, business, or industrial
plant. It is primarily composed of the distribution substation and distribution
feeders, but also contains many other pieces of equipment including reclosers,
sectionalizers, fuses and capacitors.
Electricity is "stepped down" from a high to low voltage
by transformers located at the distribution substation. These transformers
are just the reverse of those which increase the voltage at the generating
station. Electricity enters the primary side coil with the larger number
of windings and leaves from the secondary coil with the smaller number
of windings. The electricity is reduced to a lower distribution level
voltage, usually less than 39,000 volts, and distributed on three phase
lines. There are a wide variety of three phase distribution line types
and voltages supplied by electric companies across the country. A very
common three phase distribution line voltage is 12,000 volts or 12 kV.
The distribution line supplies the final step down transformer
at the customer location where the voltage is stepped down or lowered
to the service voltage for the customer's electrical system. Then the
electricity flows through the service drop to the electrical meter at
the service to be measured for billing purposes.
Distribution Transformers
Electric power leaves the distribution substation with
voltage ranging typicaly between 4,000 and 36,000 volts. This is still,
of course, too high for most typical uses, such as homes, businesses,
and even small industrial users. The device used to step this voltage
down to service voltage is yet another transformer, the distribution
transformer.
Distribution transformers operate just like large transformers
in a distribution substation. The transformer steps the voltage down
to the service voltage required by the particular customer. A normal
residential service utilities two separate voltages, 120 and 240 volts.
Several residential services are generally run from one distribution
transformer. They are sized to meet the needs of the total load of all
the customers connected to it.
Businesses and industrial plants generally do not share
transformers with other customers and require larger transformers depending
on the type and amount of electrical equipment.
Large power users involving big motors such as heavy
manufacturing companies frequently use service voltages higher than 240
volts to reduce the size and cost of their electrical equipment. Most
industrial facilities utilize 480 volts but some may require primary
line voltages due to very large motors or high energy processing needs.
Service Drop
The wires from the distribution transformer to the customer's
service point are called the "service drop". They are commonly installed
overhead, however, they can be installed underground. All conductors
must be insulated except the neutral, which may be bare in overhead installations.
Single phase service drops will have either 2 or 3 wires while three
phase service drops will have either 3 or 4 wires.
The National Electrical Code specifies installation
requirements on service-drop conductors in terms of wire size and minimum
clearances above the ground.
Service Entrance
The service entrance, as the name implies, is where
the wires connected to the load side of the meter enter the house or
building. The service entrance in a residence is commonly thought of
as a breaker or fuse box. In larger more complicated commercial or industrial
electrical systems, the service entrance may be a main disconnect panel
or a trough where up to six main switches are present.